Table 373-1
Anticipated Design Flows
Type of Use | Design Flow |
Institutions other than hospitals | 135 gpdper bed |
Golf Club | 20 gpdper locker |
Bed & Breakfast | 60 gpdper bedroom |
Shopping center/stores | 5 gpdper 100 square feet (sq.ft.) |
Hospitals | 200 gpdper bed |
Campground with 3-way hook-up | 90 gpdper site |
Campground with central comfort station | 75 gpdper site |
Motel/Hotel | 50 gpdper person, calculated at 4 persons per room |
School with gym and cafeteria | 25 gpdper student |
Factory -sanitary use only | 20 gpdper worker |
Restaurant | 40 gpdper seat |
Lounge | 20 gpdper seat |
Office space | 15 gpdper person or 15 gpd/100 sq. ft. |
N.H. Admin. Code § Env-Ws 373.08
(See Revision Note at chapter heading for Env-Ws 300); ss by #8499, eff 11-30-05