Current through Register No. 50, December 12, 2024
Section Env-Ws 372.12 - Required Source Capacity(a) The required minimum total source capacity for community water systems and those NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) shall be not less than 2 times the design flow for the water system based on a 24-hour day.(b) For small community water systems and NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) that are required to have 2 or more wells, the minimum total permitted production volume with the largest source out of service shall be equal to or greater than 50% of the system's design flow.(c) For all types of water systems, the minimum total permitted production volume shall not be less than the design flow for the water system.N.H. Admin. Code § Env-Ws 372.12
(See Revision Note at chapter heading Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12-1-05; ss by #8496, eff 11-30-05