N.H. Code Admin. R. Env-Ws 372.12

Current through Register No. 25, June 20, 2024
Section Env-Ws 372.12 - Required Source Capacity
(a) The required minimum total source capacity for community water systems and those NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) shall be not less than 2 times the design flow for the water system based on a 24-hour day.
(b) For small community water systems and NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) that are required to have 2 or more wells, the minimum total permitted production volume with the largest source out of service shall be equal to or greater than 50% of the system's design flow.
(c) For all types of water systems, the minimum total permitted production volume shall not be less than the design flow for the water system.

N.H. Code Admin. R. Env-Ws 372.12

(See Revision Note at chapter heading Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12-1-05; ss by #8496, eff 11-30-05