N.H. Admin. Code § Env-Ws 347.01

Current through Register No. 45, November 7, 2024
Section Env-Ws 347.01 - BAT for Volatile Organic Chemicals

The required technologies listed in Table 347-1 below shall be the best technology, treatment techniques, or other means available for achieving compliance with the MCL level for volatile organic chemicals (VOCs) specified in Env-Ws 315.01(a).

Table 347-1

Best Available Treatment for Volatile OrganicChemicals (VOCs)

VOC Treatment
Granular Activated Carbon(AC) Packed Tower Aeration (PT)
Benzene AC PT
Carbon tetrachloride AC PT
cis-1,2 Dichloroethylene AC PT
1,2 Dichloroethane AC PT
Trichloroethylene AC PT
Para-dichlorobenzene (1,4-Dichlorobenzene) AC PT
1,1 Dichloroethylene AC PT
Dichloromethane (Methylene chloride) PT
1,2 Dichloropropane AC PT
Ethylbenzene AC PT
Methyl tertiary-butyl ether (MtBE) AC PT
Monochlorobenzene (chlorobenzene) AC PT
o-Dichlorobenzene AC PT
Styrene AC PT
Tetrachloroethylene AC PT
Toluene AC PT
trans-1,2 Dichloroethylene AC PT
1,2,4 Trichlorobenzene AC PT
1,1,2 Trichloroethane AC PT
Trichloroethylene AC PT
1,1,1 Trichloroethane AC PT
Vinyl chloride AC
Xylene (Total) AC PT

N.H. Admin. Code § Env-Ws 347.01

(See Revision Note at chapter heading Env-Ws 300) #6521, eff 6-4-97; amd by #7261, eff 5-4-00; ss by #8497, eff 11-30-05