Section Env-Wq 713.09 - Aerated Lagoon Design: Aeration Equipment

In addition to the applicable portions of Env-Wq 713.02 through Env-Wq 713.05, aerated lagoon aeration equipment shall meet the following requirements:

(a) Aeration shall be of the diffused or mechanical mixing type; and
(b) For diffused air systems:
(1) Multiple blower units shall be provided and sized such that, with any unit out of service, the remaining units are capable of supplying all aeration needs;
(2) Means shall be provided for regulating, measuring, and recording the flow of air to the lagoons;
(3) Air diffusion piping headers and piping supports shall be corrosion-resistant with a durability for the anticipated life of the WWTP; and
(4) Ductile iron pipe headers or piping shall not be cement lined.