Section Env-Wq 705.05 - Sewage Pumping Station Design Requirements: Flow and Pump Usage Measurement(a) Sewage pumping stations with capacities of more than 250 gpm or equipped with variable speed pumps shall have continuous flow recording and totalizer capability.(b) Sewage pumping stations equipped with constant speed pumps with capacities of 250 gpm or less shall have: (1) A running meter that indicates the cumulative running time of each pump; or(2) The continuous flow recording and totalizer capability as per (a), above.N.H. Admin. Code § Env-Wq 705.05
(See Revision Note at chapter heading for Env-Wq 700) #8590, eff 3-25-06