N.H. Code Admin. R. Env-Wq 1010.04

Current through Register No. 25, June 20, 2024
Section Env-Wq 1010.04 - Backfill and Bedding For Septic Tanks
(a) Bedding material beneath a septic tank shall:
(1) Consist of at least 4 inches of sand or crushed stone placed on a firm and uniform base;
(2) Be level and compacted so as to prevent differential settling of the ground underneath the tank; and
(3) Not bear on boulders or rock edges or any aggregate in excess of 3 inches in size.
(b) Backfill around a septic tank shall be:
(1) Placed in lifts as specified by the tank manufacturer, but in no case greater than 12 inches; and
(2) Compacted in a manner that does not damage the structural integrity of the tank.

N.H. Code Admin. R. Env-Wq 1010.04

(See Revision Note at chapter heading for Env-Wq 1000) #9086, eff 2-9-08; ss by #9904-A, eff 4-16-11

Amended by Volume XXXVI Number 41, Filed October 13, 2016, Proposed by #11184, Effective 10/1/2016, Expires 10/1/2026.