Current through Register No. 45, November 7, 2024
Section Env-Or 408.11 - Limitations on Re-Use of Tanks(a) As specified in RSA 146-C:8: (1) USTs that have been removed and do not meet the requirements of Env-Or 405.01 shall not be reinstalled for the purpose of storing regulated substances; and(2) Any tank that has been used for any regulated substance shall not be reused to store food products.(b) A tank that has been used to store any regulated substance also shall not be reused to store water.(c) A tank shall be reinstalled for regulated substance storage only if: (1) As specified in RSA 146-C:8, it is: a. Thoroughly cleaned and inspected, both internally and externally;b. As a result of such cleaning and inspecting, found to be structurally sound and free of pinholes, cracks, structural damage, or corrosion; andc. Reinstalled in accordance with all applicable requirements of this chapter; and(2) Recertified by the tank manufacturer as meeting tank standards for new UST systems.(d) A tank shall not be reused as an aboveground storage tank.N.H. Admin. Code § Env-Or 408.11
(See Revision Note at chapter heading for Env-Or 400) #10393, eff 9-1-13
Amended by Volume XXXVIII Number 45, Filed November 8, 2018, Proposed by #12643, Effective 10/10/2018, Expires 10/10/2028.