Section Env-Or 406.12 - Spill Containment Integrity Testing
(a) Subject to (b), (d), and (e), below, no later than December 22, 2017 and triennially thereafter, all spill containment equipment shall be tested for tightness as specified in Env-Or 406.05 through Env-Or 406.08.
(b) Subject to (d) and (e), below, any political subdivision that did not vote to approve funding for the testing required by (a), above, shall test all spill containment equipment no later than October 13, 2021 and triennially thereafter.
(c) Subject to (d) and (e), below, no later than October 13, 2021 and triennially thereafter, all stage I system connection spill containment equipment that otherwise was not tested pursuant to (a), above, shall be tested for tightness as specified in Env-Or 406.05 through Env-Or 406.08.
(d) Spill containment equipment installed within a liquid-tight sump or of double-walled construction having electronic or mechanical interstitial monitoring that is inspected monthly pursuant to the requirements of Env-Or 406.18(a)(1) shall not be subject to the triennial integrity testing requirement of this part.
(e) Spill containment equipment installed within a secondary containment sump equipped with a sump sensor and leak monitoring in which the sump is inspected annually pursuant to Env-Or 406.18(a)(1) shall not be subject to the triennial integrity testing requirement of this part.
(f) The owner of a UST system shall report any spill containment tightness test failure to the department within 24 hours of receiving notice of the failure.
(g) The owner shall submit the following information to the department within 30 days of the closure of a failed spill containment device:
(1) A summary of closure activity, including, but not limited to, measurements from a photoionization detector; and
(2) The information required by (i), below.
(h) The owner shall submit to the department no later than 30 days after the date of the test the spill containment test information specified in (i), below, in a report generated by the owner, on a form available from the department, or on any other document containing the required information.
(i) The spill containment test report shall include the following:
(1) The information required by Env-Or 406.07(c)(1)-(6);
(2) Containment model number and manufacturer's name;
(3) Test method;
(4) Test results;
(5) Verification that the test passed or failed;
(6) Verification that the primary and secondary containment if applicable is free of debris, water, and regulated substance.
(j) The tester who has conducted the test shall sign the test report in accordance with Env-Or 406.07(e).

N.H. Admin. Code § Env-Or 406.12

(See Revision Note at chapter heading for Env-Or 400) #10393, eff 9-1-13

Amended by Volume XXXVIII Number 45, Filed November 8, 2018, Proposed by #12643, Effective 10/10/2018, Expires 10/10/2028.