N.H. Admin. Code § Env-Or 406.09

Current through Register No. 45, November 7, 2024
Section Env-Or 406.09 - Automatic Line Leak Detector Testing
(a) Automatic line leak detectors shall be tested annually in accordance with the manufacturer's requirements to confirm that they are operating in accordance with their designed function.
(b) The owner shall submit the following information in an automatic line leak detector test report generated by the owner, on a form made available by the department, or on any other document
(1) The information required by Env-Or 406.07(c)(1)-(6);
(2) Test locations; and
(3) Test results.
(c) The line leak detection tester who conducted the test shall sign the test report in accordance with Env-Or 406.07(e).
(d) When an automatic line leak detector test is performed, the owner shall send the line leak detector test report to the department no later than 30 days after the date of the test.
(e) An automatic line leak detector failure shall be indicated by a leak rate of greater than 3 gallons per hour at a pressure of 10 pounds per square inch line pressure within one hour.
(f) If any line leak detector fails the test, the owner shall remove the affected piping system(s) from service until the line leak detector is repaired or replaced and passes the line leak detector test.

N.H. Admin. Code § Env-Or 406.09

(See Revision Note at chapter heading for Env-Or 400) #10393, eff 9-1-13

Amended by Volume XXXVIII Number 45, Filed November 8, 2018, Proposed by #12643, Effective 10/10/2018, Expires 10/10/2028.