N.H. Admin. Code § Env-Dw 717.14

Current through Register No. 50, December 12, 2024
Section Env-Dw 717.14 - Compliance Monitoring for Systems with Chemical Disinfection Serving More than 3,300 People
(a) The requirements of this section shall apply to each groundwater system serving greater than 3,300 people that meets 4-log treatment using chemical disinfection.
(b) The O/O of a groundwater system that is subject to this section shall:
(1) Continuously monitor the residual disinfectant concentration using analytical methods specified in 40 CFR 141.74(a)(2) at the approved sampling location;
(2) Record the lowest residual disinfectant concentration each day that water is served to the system's customers; and
(3) Maintain the department-determined residual disinfectant concentration every day the groundwater system serves water from the groundwater saource.
(c) If a failure in the continuous monitoring equipment occurs, the O/O of a groundwater system that is subject to this section shall:
(1) Collect grab samples every 4 hours until the continuous monitoring equipment is returned to service; and
(2) Resume continuous residual disinfectant monitoring within 14 days of the failure.

N.H. Admin. Code § Env-Dw 717.14

#9600, eff 11-21-09

Amended by Volume XXXVIII Number 23, Filed June 7, 2018, Proposed by #12525, Effective 6/1/2018, Expires 6/1/2028.