Section Env-Dw 405.20 - Sizing and Installing Booster Pumps
(a) All small community water systems and those NTNC water systems important to the public health as specified in Env-Dw 405.02(g) shall comply with this section relative to booster pumps, which withdraw water from atmospheric storage tanks and pump to hydropneumatic or pressure tanks.
(b) Where booster pumps are used, t otal booster pump capacity shall be at least equal to peak flow. Booster pumps shall be in duplicate.
(c) Booster pumps shall be connected to a flat, secure surface of sufficient strength to withstand vibration, thrust, and weight. The installed elevation of the pump base shall be at least 8 inches above the finished floor in the pumphouse.