Current through Register No. 45, November 7, 2024
Section Env-A 3510.02 - Small, Remote HMIWI Inspection CoverageInspections pursuant to Env-A 3510.01 shall include the following:
(a) Inspection of all burners, pilot assemblies, and pilot sensing devices for proper operation;(b) Proper adjustment of primary and secondary chamber combustion air flow;(c) Inspection of hinges and door latches;(d) Inspection of dampers, fans, and blowers for proper operation;(e) Inspection of HMIWI door and door gaskets for proper sealing;(f) Inspection of motors for proper operation;(g) Inspection of primary chamber refractory lining;(h) Inspection of incinerator shell for corrosion and hot spots;(i) Inspection of secondary/tertiary chamber and stack;(j) Inspection of mechanical loader, including limit switches, for proper operation, if applicable;(k) Visual inspection of waste bed grates;(l) For the burn cycle that follows the inspection, documentation that the incinerator is operating properly and that any necessary adjustments have been made;(m) Inspection of air pollution control device or devices for proper operation, if applicable;(n) Inspection of waste heat boiler systems to ensure proper operation, if applicable;(o) Inspection of bypass stack components;(p) Proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and(q) General observation that the equipment is maintained in good operating condition.N.H. Admin. Code § Env-A 3510.02