N.H. Code Admin. R. Env-A 1806.04

Current through Register No. 25, June 20, 2024
Section Env-A 1806.04 - Abatement of Asbestos-Containing Cementitious Roofing or Siding Materials

Facility O/Os who remove cementitious ACM from the side or roof of a building and who do not sand, saw, cut, drill, or otherwise treat the ACM in a manner that might create a fine dust or particles, may abate such materials by complying with the following in lieu of Env-A 1805.04, Env-A 1805.05, Env-A 1805.07, and Env-A 1805.09:

(a) The contractor and workers shall be licensed and certified in accordance with Env-A 1810;
(b) The surrounding ground shall first be protected with poly drop cloths such that no ACM can come into contact with the ground;
(c) All ACM shall be adequately wetted before removal and maintained wet during and after removal to prevent the release of fibers until placed into leak-tight containers for disposal;
(d) Cementitious ACM shall be removed intact, to the extent possible, by prying out or cutting fasteners;
(e) Cementitious ACM shall be carefully lowered to the ground, not dropped or thrown; and
(f) All ACM waste shall be packaged, labelled, and disposed of in accordance with Env-A 1805.08.

N.H. Code Admin. R. Env-A 1806.04

Derived From Volume XXXVII Number 19, Filed May 11, 2017, Proposed by #12172, Effective 5/5/2017, Expires 5/5/2027.