Nev. Admin. Code § 455C.206

Current through December 31, 2024
Section 455C.206 - Gas burners

For installations which are gas-fired:

1. The burners used must conform to the applicable requirements of the National Fuel Gas Code, as adopted by reference in NAC 455C.108; and
2. An emergency shut-off valve must be installed:
(a) On the gas line which feeds the installation;
(b) In a location on that gas line such that the emergency shut-off valve is upstream of all other valves; and
(c) Not more than 5 feet from the point where the gas line enters the room for the boiler or, if such an installation is not possible, as close to the point where the gas line enters the room as possible.

The emergency shut-off valve must interrupt all flow of gas to the installation upon the actuation of the emergency shut-down switch for the boiler.

Nev. Admin. Code § 455C.206

Added to NAC by Div. of Industrial Relations by R101-02, eff. 12-15-2004; A by R045-20A, eff. 10/26/2020; A by R034-21A, eff. 7/26/2023