Current through December 12, 2024
Section 445A.27612 - Reuse category A+: Water quality requirements1. Reclaimed water that is used for an activity approved for reuse category A+ must meet the following water quality requirements: (a) The provisions of the "National Primary Drinking Water Regulations" and related federal regulations adopted by reference in NAC 445A.4525.(b) The secondary maximum contaminant levels specified in NAC 445A.455.(c) Twelve-log enteric virus reduction, which must be demonstrated from the point where raw sewage enters a treatment works to the point of extraction from an aquifer for potable use.(d) Ten-log Giardia lamblia cyst reduction and ten-log Cryptosporidium oocyst reduction, which must be demonstrated from the point where raw sewage enters a treatment works to the zone of saturation.2. Where reclaimed water in reuse category A+ is used for indirect potable reuse, the point of compliance for paragraphs (a) and (b) of subsection 1 is the zone of saturation.Nev. Admin. Code § 445A.27612
Added to NAC by Environmental Comm'n by R101-16A, eff. 12/21/2016