Nev. Admin. Code § 445A.6722

Current through August 29, 2024
Section 445A.6722 - Cross-connections and backflow: Design of fire sprinkler system

The designer of a fire sprinkler system shall ensure that, based upon the placement of any reduced pressure principle assembly or reduced pressure detector assembly:

1. An antifreeze loop or the total line of the fire sprinkler system is able to accommodate the thermal expansion of any antifreeze; or
2. If necessary, an expansion tank is provided to accommodate the thermal expansion of any antifreeze.

Nev. Admin. Code § 445A.6722

Added to NAC by Bd. of Health, eff. 2-20-97

NRS 445A.860