Nev. Admin. Code § 445A.6692

Current through August 29, 2024
Section 445A.6692 - Water wells: Access port or sounding tube; vent
1. Except as otherwise provided in subsection 2, a water well must have an access port which can be used for measuring the level of water. If the diameter of the casing is:
(a) No greater than 8 5/8 inches, the access port must:
(1) Be 1 inch in diameter and located at the top or in the cover of the casing; and
(2) Have a removable plug or bolt installed in such a manner as to prevent pollutants and contaminants from entering the well.
(b) Greater than 8 5/8 inches, the access port must:
(1) Be 2 inches in diameter and located near the top of the casing; and
(2) Have a watertight, screw-type cap which is:
(I) Sealed in such a manner as to prevent pollutants and contaminants from entering the well; and
(II) Kept sealed when not being used for measuring the level of water.
2. If the diameter of the casing of a water well is greater than 8 5/8 inches, the well may be equipped with a sounding tube, in lieu of an access port, which is:
(a) Not less than 3/4 inch nor more than 1 inch in diameter; and
(b) Installed in such a manner as to:
(1) Preclude the entanglement of the sounder around the drop pipe or in the wires of any submersible pump; and
(2) Prevent any interference with cascading water.
3. A water well must be equipped with:
(a) A vent that:
(1) Extends above the wellhead;
(2) Is elbowed toward the ground in the shape of an inverted "J"; and
(3) Is covered with a screen that is not susceptible to damage by corrosion and has not less than 22 nor more than 24 mesh per inch; or
(b) An air and vacuum valve that is attached to discharge piping.

Nev. Admin. Code § 445A.6692

Added to NAC by Bd. of Health, eff. 2-20-97

NRS 445A.860