A homeowner plans to build a 4-bedroom house. Percolation testing yields percolation rates of 15 minutes per inch in test hole number one and 23 minutes per inch in test hole number two. To determine the required capacity of the wastewater treatment tank, the required number of square feet of disposal area, and the required number of lineal feet of absorption trench:
Step 1 - Pursuant to the table in subsection 1 of NAC 444.8306, a septic or wastewater treatment tank that has a capacity of 1,200 gallons is required for a 4-bedroom house.
Step 2 - The slowest percolation rate, which is 23 minutes per inch, must be used to determine the design application rate. Pursuant to the table in subsection 9 of NAC 444.8354, the design application rate is 1.0 gallon per square foot.
Step 3 - The required absorption area is calculated by dividing the capacity of the septic or wastewater treatment tank by the design application rate as follows:
1,200 gallons / 1.0 gallon/square foot = 1,200 square feet
Step 4 - The effective sidewall area must be calculated by multiplying the number of feet of aggregate beneath the distribution line by 2, to utilize the absorption area on each side of the trench. For the purposes of this example, assume that a maximum of 4 square feet of the area of the sidewall will be utilized on each trench wall per each lineal foot as follows:
2 * 4 square feet = 8 square feet per each lineal foot of trench
Step 5 - The required trench length is now determined by dividing the required absorption area by the effective sidewall area as follows:
1,200 square feet / 8 square feet/lineal foot = 150 lineal feet
Since the maximum length of a distribution line may not exceed 110 feet, a minimum of two trenches of equivalent lengths are required. Therefore, the use of two distribution lines that are 75 feet long with 4 feet of aggregate beneath the distribution lines would be acceptable.
Nev. Admin. Code § 444.8352
NRS 439.200, 444.650