229 Neb. Admin. Code, ch. 20, § 007

Current through September 17, 2024
Section 229-20-007

One or more safety valves on every power boiler shall be set at or below the maximum allowable working pressure. The remaining valves may be set within a range of three percent above the maximum allowable working pressure but, the range setting of all the safety valves on a power boiler shall not exceed ten percent of the highest pressure at which any valve is set.

229 Neb. Admin. Code, ch. 20, § 007

Adopted effective 8/7/2016.