229 Neb. Admin. Code, ch. 20, § 005

Current through September 17, 2024
Section 229-20-005

No valves of any type shall be placed between the safety valve and the power boiler. If a discharge pipe is used, no valve shall be placed on the discharge pipe between the safety valve and the atmosphere. The discharge pipe shall be at least the full size of the safety valve discharge and fitted with an open drain to prevent water lodging in the upper part of the safety valve or discharge pipe. The discharge pipe shall be as short and straight as possible and so arranged as to avoid undue stress on the valve or valves. All safety valve discharges shall be so located or piped as to be carried away from walkways or platforms.

229 Neb. Admin. Code, ch. 20, § 005

Adopted effective 8/7/2016.