229 Neb. Admin. Code, ch. 16, § 002

Current through September 17, 2024
Section 229-16-002

Before a used or secondhand boiler or pressure vessel can be installed or shipped into this state, an inspection must be made by the Chief Inspector or a Deputy Inspector or by an owner/user inspection organization inspector. This inspection shall consist of an internal, external and a hydrostatic test to 100% of maximum allowable working pressure (MAWP) as identified on the nameplate or design/data report. This inspection report shall be filed with the Chief Inspector. For secondhand or used boilers or pressure vessels that are to be shipped and installed into this state, if the boiler or pressure vessel has a current certificate of inspection from another state, a copy of that certificate and a copy of the last two inspections shall be supplied to the Chief Boiler Inspector to determine the installation inspection requirements.

229 Neb. Admin. Code, ch. 16, § 002

Amended effective 8/7/2016.