Section 175-6-006 - CONSTRUCTIONIn new construction, the licensee must:
(A) Provide a conveniently located sink for soaking and hand washing of laundry when laundry services are provided on-site at the children's day health service;(B) Ensure the door of a toilet, changing, or bathing room with less than 50 square feet of clear floor area and dedicated to consumer use must not swing inward;(C) Ensure curtain layout must totally surround each care and treatment location which will not restrict access to the entrance to the room, lavatory, toilet, or enclosed storage facilities;(D) Ensure electrical systems have ground fault circuit interrupter protected outlets in all wet areas and within 6 feet of all hand washing sinks;(E) Ensure mechanical exhaust ventilation at a rate of 10 air exchanges per hour for windowless toilets, changing and bathing areas, laundry rooms, housekeeping rooms, and kitchens; and(F) Ensure mechanical exhaust ventilation at a rate of 5 air exchanges per hour for care, treatment, and service areas.175 Neb. Admin. Code, ch. 6, § 006