Table 15-1
Process Weight Rate | Rate of Emissions | Process Weight Rate | Rate of Emissions | ||
lb/hr | tph | lb/hr | lb/hr | tph | lb/hr |
100 | 0.05 | 0.551 | 16,000 | 8.000 | 16.5 |
200 | 0.10 | 0.877 | 18,000 | 9.00 | 17.9 |
400 | 0.20 | 1.40 | 20,000 | 10. | 19.2 |
600 | 0.30 | 1.83 | 30,000 | 15. | 25.2 |
800 | 0.40 | 2.22 | 40,000 | 20. | 30.5 |
1,000 | 0.50 | 2.58 | 50,000 | 25. | 35.4 |
1,500 | 0.75 | 3.38 | 60,000 | 30. | 40.0 |
2,000 | 1.00 | 4.10 | 70,000 | 35. | 41.3 |
2,500 | 1.25 | 4.76 | 80,000 | 40. | 42.5 |
3,000 | 1.50 | 5.38 | 90,000 | 45. | 43.6 |
3,500 | 1.75 | 5.96 | 100,000 | 50. | 44.6 |
4,000 | 2.00 | 6.52 | 120,000 | 60. | 46.3 |
5,000 | 2.50 | 7.58 | 140,000 | 70. | 47.8 |
6,000 | 3.00 | 8.56 | 160,000 | 80. | 49.0 |
7,000 | 3.50 | 9.49 | 200,000 | 100. | 51.2 |
8,000 | 4.00 | 10.4 | 1,000,000 | 500. | 69.0 |
9,000 | 4.50 | 11.2 | 2,000,000 | 1,000. | 77.6 |
10,000 | 5.00 | 12.0 | 6,000,000 | 3,000. | 92.7 |
12,000 | 6.00 | 13.6 |
Table 15-2
Total Heat Input in Million British Thermal Units Per Hour (MMBtu/hr) | Maximum Allowable Emissions of Particulate Matter in Pounds per Million British Thermal Units (lb/MMBtu) |
10 or less | 0.60 |
Between 10 and 10,000 | 1.026 I 0.233 I = The total heat input in MMBtu/hr |
10,000 or more | 0.12 |
129 Neb. Admin. Code, ch. 15, § 001