Rule 37.96.409 - FIRE SAFETY REQUIREMENTS
(1) Licensed child care facilities must meet International Fire Code requirements to open and operate as a child care facility. New child care center, school-age care, or drop-in care providers should consult with their local jurisdiction or state fire marshal before selecting a facility.
(2) Licensed child care providers must provide CCL an annual inspection report from the state or local jurisdiction fire marshal indicating the fire safety rules have been met.
(a) Providers using a commercial or public space that receive an annual fire safety inspection, such as a school, do not need a separate inspection. The child care provider is responsible for providing a copy of the inspection reports to CCL.
(3) Group child care, family child care, and FFN providers must meet fire safety requirements by:
(a) having a fire extinguisher that:
(i) is easily accessible on each floor level that is used by the child care;
(ii) has a minimum level of extinguisher classification of 2A10BC with a hose; and
(iii) is installed and maintained in accordance with the manufacturer's specifications;
(b) having operational UL smoke alarms on each floor of the facility that is used for child care that are:
(i) installed in accordance with the manufacturer's specifications;
(ii) installed in front of the doors to stairways, in corridors of all floors, and in all rooms where children sleep; and
(iii) tested at least once a month to ensure that they are operating correctly and replaced every ten years or in accordance with the manufacturer's instructions;
(c) ensuring all wood burning stoves meet building codes and have a protective enclosure if used during the hours of care;
(d) not using portable electric or unvented fuel-fired heating devices, and ensuring all radiators, if too hot to touch, have a protective enclosure; and
(e) using extension cords according to the manufacturer's specifications and not using extension cords to supply electricity to equipment or appliances that are fixed in place.