Maximum Allowable Emissions of | ||
Particulate Matter in lbs. per | ||
Million British Thermal Units | ||
Heat Input in Million | Existing | New |
British Thermal Units | Fuel Burning | Fuel Burning |
per Hour | Equipment | Equipment |
10 and below | 0.60 | 0.60 |
100 | 0.40 | 0.35 |
1,000 | 0.28 | 0.20 |
10,000 and above | 0.19 | 0.12 |
For existing fuel burning equipment: E = 0.882 * H-0.1664
For new fuel burning equipment: E = 1.026 * H-0.233
Where H is the heat input capacity in MMBtu per hour and E is the maximum allowable particulate emissions rate in lbs. per MMBtu.
For the purposes of this rule, heat input will be calculated as the aggregate heat content of all fuels (using the upper limit of their range of heating value) whose products of combustion pass through the stack or chimney.
Mont. Admin. r. 17.8.309
75-2-111, 75-2-203, MCA; IMP, 75-2-203, MCA;