Mo. Code Regs. tit. 10 § 23-3.030

Current through Register Vol. 49, No. 20, October 15, 2024
Section 10 CSR 23-3.030 - [Effective 11/30/2024] Standards for Construction of Water Wells

PURPOSE: This rule describes the minimum construction standards for water wells.

PUBLISHER'S NOTE: The secretary of state has determined that the publication of the entire text of the material which is incorporated by reference as a portion of this rule would be unduly cumbersome or expensive. This material as incorporated by reference in this rule shall be maintained by the agency at its headquarters and shall be made available to the public for inspection and copying at no more than the actual cost of reproduction. This note applies only to the reference material. The entire text of the rule is printed here.

(1) Domestic Water Wells and Pilot Holes.
(A) Casing.
1. Steel well casing. The minimum standards for steel casing are found in Table 3.2

Table 3.2 Minimum standards for steel casing.

Nominal Pipe

Outside Diameter

Wall Thickness

(Inches)

(Inches)

(Inches)

(Weight (lbs.)/Foot)

4

4 1/2

0.188

9

5

5 1/2

0.188

10

6

6 5/8

0.188

13

8

8 5/8

0.188

17

10

10 3/4

0.188

21

12

12 3/4

0.188

25

14

14

0.188

28

16

16

0.188

32

A. Joints. Joints shall be welded or threaded and be watertight. Recessed or reamed and drifted couplings shall be used on threaded casing. Other couplings may be used provided the design, taper, and type of thread of the coupling matches that of the pipe. Casing extension material shall be of similar material to the original casing. Other types of joints or devices used to join dissimilar casing extension materials may be used upon receiving prior written approval from the department.
B. Standards. Casing shall be new, which includes used casing that was salvaged from a water supply well within ninety (90) days of installation and is decontaminated. Casing shall meet one (1) of the following requirements:
(I) Grade A or B of the American Society for Testing and Materials (ASTM) A53-A53M-20 Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless. This standard is incorporated by reference as published July 15, 2020, by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 and does not incorporate any subsequent amendments or additions;
(II) Grade A or B of ASTM A500/A500M-21 Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes. This standard is incorporated by reference as published January 21, 2021, by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 and does not incorporate any subsequent amendments or additions;
(III) ASTM A589-A589M-06 Standard Specification for Seamless and Welded Carbon Steel Water-Well Pipe. This standard is incorporated by reference as published October 2, 2018, by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 and does not incorporate any subsequent amendments or additions; or
(IV) Any other new pipe having a quality equal to or greater than those specified above.
C. Drive shoe.
(I) In areas where steel casing is required, equip the well casing with a drive shoe or similar protective device to prevent damage to the well casing during construction of the well.
(II) If no drive shoe is used, follow the minimum grout cure times in Table 3.3.

Table 3.3 Minimum Cure Times for Grout

Grout Type

Minimum Cure Time (hours)

Hi early cement

12

Portland Type I cement

72

Chipped Bentonite

4

High Solids Bentonite Slurry

*

*Follow manufacturer's guidelines. Cure time will vary based on additives.

D. Installation. Install and centralize casing within the borehole for even distribution of grout material.
2. Plastic well casing. The minimum standards for plastic well casing are found in Table 3.4.

Table 3.4 Minimum standards for plastic casing.

Nominal Pipe

Outside Diameter

Standard Dimension Ratio

Schedule

(Inches)

(Inches)

(SDR)

(SCH)

4

4 1/2

26

40

5

5 1/2

26

40

6

6 5/8

26

40

A. Joints. Well casing joints shall be watertight and joined by solvent weld (glued) or mechanical. Casing extension material shall be of similar material to the original casing. Other types of joints or devices used to join dissimilar casing extension materials may be used upon receiving prior written approval from the department.
B. Standards. Casing shall be new and meet ASTM F480-14 Standard Specification for Thermoplastic Well Casing Pipe and Couplings Made in Standard Dimension Ratios (SDR), SCH 40 and SCH 80. This standard is incorporated by reference as published March 1, 2014, by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 and does not incorporate any subsequent amendments or additions. Used casing is considered new when salvaged from a water supply well within ninety (90) days of installation and decontaminated.
C. Packers. A packer, coupling, or inverted bell shall be secured at the bottom of the casing and hold the grout in place while drilling continues. No packer, coupling, or inverted bell is needed if grout is allowed to cure following minimum cure times in Table 3.3.
D. Installation. Casings shall be installed and centralized within the borehole for even distribution of grout material.
3. Concrete and fiberglass well casing -
A. May be used for unconsolidated wells greater than eighteen inches (18") in diameter;
B. Shall be composed of non-toxic durable material designed for use in potable water wells; and
C. Shall be installed and centralized within the borehole for even distribution of grout material.
4. Other materials may be used upon receiving prior written approval from the department.
(B) Borehole. For borehole size see 10 CSR 23-3.090.
(C) Grouting. It is the responsibility of the well installation contractor to ensure that the annular space is sealed and that the casing does not leak. This responsibility ends three (3) years after the approval date by the department unless it can be proven that the annular seal has been damaged by other persons.
1. Grouting installation methods.
A. Gravity method.
(I) Bentonite granules or bentonite slurry shall not be poured through standing water greater than one hundred feet (>100').
(II) Table 3.5 states the maximum depth that grout can be gravity-fed into the well annulus.

Table 3.5 Maximum Gravity Grouting Depths

Annular Space

Gravity Feed Depth

(inches)

(feet)

1

100

1 1/16

106

1 1/8

112

1 3/16

119

1 1/4

125

1 5/16

131

1 3/8

137

1 7/16

144

1 1/2

150

1 1/16

156

1 5/8

162

1 11/16

169

1 3/4

175

1 13/16

181

1 7/8

187

1 15/16

193

2

200

(III) Gravity grouting greater than two hundred feet (200') in a four inch (4") annulus is not allowed.
B. Tremie method. Tremie pipes shall be -
(I) Placed into the annulus and extend to no less than five feet (5') from the bottom of the interval to be grouted;
(II) Gradually withdrawn as the grouting material is emplaced; and
(III) No greater than ten feet (10') above the emplaced grouting material during the entire grouting process.
C. Tremie pressure method. The tremie pipe shall remain submerged in the grouting material during the entire grout pumping process.
D. Pressure method.
E. Open-hole method.
(I) Non-slurry bentonite may be poured from the surface and allowed to completely hydrate before the casing is installed.
(II) Bentonite slurry may be used in wells with more than one hundred feet (>100') of standing water only if the grout is emplaced by one (1) of the tremie grouting methods.
F. Positive displacement method.
(I) Bentonite slurry or cement slurry may be used in wells with more than one hundred feet (>100') of standing water only if the grout is emplaced by one (1) of the tremie grouting methods.
G. Other grouting methods may be used upon receiving prior written approval from the department.
2. Grout materials.
A. Cement slurry.
B. Bentonite slurry.
C. Bentonite non-slurry. If there is no water in the annular space, the bentonite shall be hydrated.
D. Other grout types may be used upon receiving prior written approval from the department.
(D) Driving Casing.
1. When geologic conditions require the casing to be driven, the casing may be driven to the casing depth without adding grout.
2. When it is necessary to drive multiple strings of smaller diameter casing through the primary casing, each succeeding smaller diameter casing shall extend into the preceding casing at least twenty feet (20').
3. Once the casing is set, install liner pursuant to 10 CSR 23-3.080(3)(C).
4. In addition to the liner, a top annular casing seal, at least ten feet (10') deep is required below the pitless connection.
5. A liner and top annular seal are not required when the open hole method or positive displacement grouting method is used.
(E) Wellhead Completion. Follow well casing seal and connection installation pursuant to 10 CSR 23-3.050(6).
(2) Multifamily Wells.
(A) Multifamily wells shall have no more than eight (8) connections, fewer than twenty-five (25) individuals, and have a pumping capacity of less than seventy gallons per minute (<70 gpm).
(B) Multifamily wells may be used to serve a charitable or benevolent organization pursuant to section 640.116, RSMo.
(C) Casing.
1. Follow 10 CSR 23-3.090 for minimum casing depths by Drilling Area for domestic water wells.
2. Install new casing that meets the requirements listed in 10 CSR 23-3.030(1) (A) 1. or new Standard Dimension Ratio 21, or SCH 80 plastic casing meeting the requirements of 10 CSR 23-3.030(1) (A) 2.B.
3. Other casing design or materials may be used upon receiving prior written approval from the department.
4. Liners are not a substitute for casing.
(D) Joints.
1. Steel well casing joints shall be welded or threaded and be watertight. Other types of joints may be used upon receiving advanced written approval by the department. Recessed or reamed and drifted couplings shall be used on threaded casing; other couplings may be used provided the design, taper, and thread type is compatible with the pipe.
2. Plastic well casing joints shall be watertight and joined by solvent weld (glued) or mechanically.
3. Casing extension material shall be of similar material to the original casing. Other types of joints or devices used to join dissimilar casing extension materials may be used upon receiving prior written approval from the department.

(E) Drive shoe. For drive shoe requirements see 10 CSR 23-3.030(1)(A) 1.C.
(F) Packers. For packer requirements see 10 CSR 23-3.030(1)(A) 2.C.
(G) Installation. Casings shall be installed and centralized within the borehole for even distribution of grout material.
(H) Borehole. The borehole must be a minimum of four inches (4") larger in diameter than casing.
(I) Grouting. Grout the annular space of the well full length. It is the responsibility of the well installation contractor to ensure that the annular space is sealed and that the casing does not leak. This responsibility ends three (3) years after the date of approval by the department unless it can be proven that the well seal has been damaged by another person.
1. Grouting installation methods.
A. Tremie method pursuant to 10 CSR 23-3.030(1)(C) 1.B.
B. Tremie pressure method pursuant to 10 CSR 23-3.030(1)(C) 1.C.
C. Pressure method pursuant to 10 CSR 23-3.030(1)(C) 1.D.
2. Grout materials.
A. Grout types pursuant to 10 CSR 23-3.030(1)(C) 2. may be used except powdered or granular non-slurry bentonite.
B. Other grout types may be used upon receiving prior written approval from the department.
(J) Wellhead Completion. The wellhead shall be completed pursuant to 10 CSR 23-3.050(6).
(3) High yield bedrock wells or high yield unconsolidated wells two hundred feet (200') or more in depth.
(A) Casing.
1. The minimum amount of casing shall be determined by the department in advance.
2. Install new steel casing that meets the minimum standards specified in Table 3.6 for size and weight.
3. In lieu of steel casing, unconsolidated wells two hundred feet (200') or more in depth may use Schedule 80 or Standard Dimension Ratio 21 (SDR 21) plastic casing.
4. Liners are not a substitute for casing.
5. Other design or materials may be used upon receiving prior written approval from the department.

Click to view image

(B) Joints, Standards, Drive Shoe, Borehole, and Wellhead Completion shall be followed pursuant to 10 CSR 23-3.030(2).
(C) Grouting.
1. Grout the annular space of the well full-length with neat cement. It is the responsibility of the well installation contractor to ensure that the annular space is sealed and that the casing does not leak. This responsibility ends three (3) years after the date of approval by the department unless it can be proven that the well seal has been damaged by another person.
2. Grouting installation methods.
A. Tremie method pursuant to 10 CSR 23-3.030(1) (C) 1.B.
B. Tremie pressure method pursuant to 10 CSR 23-3.030(1)(C) 1.C.
C. Pressure method pursuant to 10 CSR 23-3.030(1) (C) 1.D.
(4) High yield unconsolidated wells less than two hundred feet (<200').
(A) Casing.
1. Install a minimum of twenty feet (20') of casing.
2. Install new steel or plastic casing that meets the minimum standards specified in Table 3.2 or Table 3.4, respectively.
3. Install and centralize casing within the borehole for even distribution of grout material.
4. Other design or materials may be used upon receiving prior written approval from the department.
(B) Borehole. Construct the borehole pursuant to 10 CSR 23-3.030(2)(H).
(5) Public Water Supply Wells.
(A) Wells that serve a public water system shall not be constructed or altered without authorization pursuant to 10 CSR 60-3.
(6) Oil and Gas Zones.
(A) Report oil or gas encounters and the conversion of water wells to oil or gas wells pursuant to section 256.614, RSMo.
(B) Any water well that encounters oil and/or gas shall have an annular or open hole grout plug from fifty feet (50') below the oil and/or gas bearing zone to fifty feet (50') above the oil and/or gas bearing zone.
(C) The grout plug shall be composed of cement slurry with a two to six percent (2-6%) bentonite additive.
(D) The grout plug shall be placed via one (1) of the tremie methods.

10 CSR 23-3.030

AUTHORITY: sections 256.606, 256.614, 256.615and256.626, RSMo 1994.* Original rule filed April 2, 1987, effective 7/27/1987. Emergency amendment filed Nov. 16, 1993, effective 12/11/1993, expired 4/9/1994. Amended: Filed Aug. 17, 1993, effective 3/10/1994. Amended: Filed July 13, 1994, effective 1/29/1995. Amended: Filed Nov. 1, 1995, effective 6/30/1996.
Amended by Missouri Register January 15, 2019/Volume 44, Number 2, effective 2/28/2019
Amended by Missouri Register October 1, 2024/volume 49, Number 19, effective 11/30/2024.

*Original authority: 256.606, RSMo 1991; 256.614, RSMo 1985, amended 1991; 256.615, RSMo 1991; and 256.626, RSMo 1985, amended 1991.