Rule 15-16-1-83.20.3 - Lighting

Each resident's room shall have artificial light adequate for reading and other uses as needed. There should be a minimum brightness of ten (10) foot candles of lighting for general use in residents' rooms and a minimum brightness of thirty (30) foot candles of lighting for reading purposes. All entrances, hallways, stairways, ramps, cellars, attics, storerooms, kitchens, laundries, and service units shall have sufficient artificial lighting to prevent accidents and promote efficiency of service. Night lights shall be provided in all hallways, stairways, toilets, and bathing rooms.