Rule 15-16-1-49.19.7 - Toilet and Bathing Facilities in an ICF-IID1. Lavatory, toilet and bathing facilities shall be provided in each ICF-IID nursing unit as follows: a. Bathing Facilities | 2 per nursing unit |
b. Combination toilet and lavatory | 2 per nursing unit |
2. As a minimum, showers shall be thirty (30) inches by sixty (60) inches without curbing.3. Handrails shall be provided for all tubs, showers, and commodes in an ICF-IID and/or an ICF-IID Residential Community Home.4. In addition to the requirements set forth above, a lavatory shall be provided in each client bedroom or in a toilet room that is directly accessible from the bedroom in an ICF-IID.5. In addition to the requirements set forth above, a toilet shall be located in a room directly accessible from each client bedroom in an ICF-IID. The minimum area for a room containing only a toilet shall be three (3) feet by six (6) feet in an ICF-IID.15 Miss. Code. R. 16-1-49.19.7
Miss. Code Ann. § 43-11-13