Rule 15-16-1-48.22.5 - Exit Doors

Exit doors shall meet the following:

1. At least two (2) remotely located exits shall be provided for each occupied story of a facility.
2. Dead end hallways in excess of twenty (20) feet are not allowed.
3. Doors to the exterior shall be not less than thirty-six (36) inches wide and egress shall not be impeded by being locked.
4. Exit doors shall swing in the direction of exit and shall not obstruct the travel along any required exit.
5. Doors leading to stairways shall be not less than thirty-six (36) inches wide.
6. Revolving doors shall not be used as required exits.