Rule 15-16-1-45.40.4 - Lighting

Each resident's room shall have artificial light adequate for reading and other uses as needed. There should be a minimum of ten (10) foot-candles of lighting for general use in resident's room and a minimum of thirty (30) foot-candles of lighting for reading purposes. All entrances, corridors, stairways, ramps, cellars, attics, storerooms, kitchens, laundries, and service units shall have sufficient artificial lighting to prevent accidents and promote efficiency of service. Night lights shall be provided in all corridors, stairways, toilets, and bathing rooms.