15 Miss. Code. R. 16-1-44.31.18

Current through December 10, 2024
Rule 15-16-1-44.31.18 - Interior Finish and Decorative Materials

All combustible decorative and acoustical material to include wall paneling shall be as follows:

1. Materials on wall and ceiling in corridors and rooms occupied by four or more persons shall carry a flame spread rating of 25 or less and a smoke density rating of 450 or less in accordance with ASTM E-84.
2. Rooms occupied by less than four persons shall have a flame spread rating of 75 or less and a smoke density rating of 450 or less in accordance with ASTM E-84.

15 Miss. Code. R. 16-1-44.31.18

Miss. Code Ann. § 41-75-13