Rule 15-10-76-3.4.22 - Fired Storage Water Heaters and Supply Vessels
1. Minimum Controls -- All fired storage water heaters and supply vessels shall be equipped with the following controls and devices:
a. Operating temperature control;
b. High-limit temperature control;
c. Positive flame failure cut-off;
d. Approved pressure-temperature relief valve, set at or below the safe working pressure of the vessel, with such setting satisfactory for the application.
2. Location -- All fired vessels and heaters shall be so located as to provide access to the controls, safety relief valve and drain.
3. Discharge Lines -- When a discharge line from a relief valve is installed, it shall not be reduced but shall be full size and be piped to a safe location, graded down.
4. Relief Valve Testing -- The operator shall manually test the relief valve once each month.
5. Alternative Use -- Storage water heaters and supply vessels, fired or unfired, shall not be used as a heating boiler.