Minn. R. Part 7151.5600

Current through Register Vol. 48, No. 50, June 10, 2024
Part 7151.5600 - CORROSION PROTECTION
Subpart 1.Tanks.

The floor of a steel aboveground storage tank must be protected from corrosion using one of the following methods:

A. the tank is elevated so that the underside of the tank floor is not in contact with any surface other than the tank supports;
B. the tank rests on a continuous concrete slab that is designed to prevent water from accumulating under the tank floor;
C. the tank is double walled;
D. the tank is double-bottomed with:
(1) a vacuum pulled on the interstitial space; or
(2) a cathodic protection system installed in the interstitial space;
E. the tank floor is:
(1) cathodically protected; and
(2) internally lined in accordance with American Petroleum Institute Standard 652;
F. the tank floor is:
(1) cathodically protected; and
(2) internally inspected in accordance with American Petroleum Institute Standard 653; or
G. the tank floor is:
(1) internally lined in accordance with American Petroleum Institute Standard 652; and
(2) internally inspected in accordance with American Petroleum Institute Standard 653.
Subp. 2.Lines.

A steel line must be protected from external corrosion using one of the following methods:

A. the line is not in contact with soil;
B. the line is cathodically protected; or
C. the line is double walled.
Subp. 3.Design criteria.

Cathodic protection of new steel tanks and lines must meet the following design criteria:

A. the cathodic protection system must be designed by a corrosion expert in accordance with American Petroleum Institute Standards 651 and 1632, as applicable; and
B. underground lines and the underside of the floor of a shop-fabricated steel tank must be coated with dielectric material in accordance with Steel Tank Institute Recommended Practice R893-89.

Minn. R. Part 7151.5600

23 SR 883; 25 SR 556

Statutory Authority: MS s 115.03