Minn. R. Part 7511.2703

Current through Register Vol. 48, No. 51, June 17, 2024
Part 7511.2703 - SECTION 2703, GENERAL REQUIREMENTS
Subpart 1.IFC Section 2703.8.3.4.

IFC Section 2703.8.3.4 is amended to read:

2703.8.3.4 Separation.The required fire-resistance rating for fire barrier assemblies shall be in accordance with Table 2703.8.3.2.
Subp. 2.IFC Section 2703.8.3.

IFC Section 2703.8.3 is amended by adding a section to read:

2703.8.3.6 Hazardous materials above the third floor in laboratories in Group B, E or I-2 occupancies. Control areas containing laboratories located above the third floor in Group B, E or I-2 occupancies may be exempted from the provisions of Sections 2703.8.3.1, 2703.8.3.3, and 2703.8.3.4 provided the following conditions are met:
1. The buildings containing the laboratories are equipped throughout with automatic sprinkler protection installed in accordance with Section 903.3.1.1.
2. Control areas containing laboratories located above the third floor are separated from each other and other portions of the building by a fire barrier having a fire-resistance rating of not less than two hours.
3. The maximum amount of hazardous materials in storage and use in control areas containing laboratories does not exceed 10 percent of the maximum allowable quantities listed in Tables 2703.1.1(1) and 2703.1.1(2) with all increases allowed in the footnotes of those tables.
4. The maximum number of control areas containing laboratories shall not exceed 5 per floor.

Minn. R. Part 7511.2703

32 SR 10

Statutory Authority: MS s 299F.011