Minn. R. Part 7511.1018

Current through Register Vol. 48, No. 51, June 17, 2024
Part 7511.1018 - SECTION 1018, AISLES

IFC section 1018 and all subsections are deleted in their entirety and replaced with the following:

SECTION 1018

AISLES

1018.1Aisles and aisle accessways. Aisles and aisle accessways serving as a portion of the exit access in the means of egress system shall comply with the requirements of this section. Aisles and aisle accessways shall be provided from all occupied portions of the exit access. Aisles and aisle accessways serving assembly areas, other than seating at tables, shall comply with Section 1029. Aisles and aisle accessways serving reviewing stands, grandstands, and bleachers shall comply with Section 1029.
1018.2Width determination. Where tables or counters are served by fixed seats, the width of the aisle or aisle accessway shall be measured from the back of the seat. Where seating is located at a table or counter and is adjacent to an aisle or aisle accessway, the measurement of required clear width of the aisle or aisle accessway shall be made to a line 19 inches (483 mm) away from and parallel to the edge of the table or counter. The 19-inch (483 mm) distance shall be measured perpendicular to the side of the table or counter. In the case of other side boundaries for aisle or aisle accessways, the clear width shall be measured to walls, tread edges, or other obstructions. The required width of aisles and aisle accessways shall be unobstructed.

Exception: Doors, when fully opened, and handrails shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections, such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) from each side.

1018.2.1Minimum aisle accessway width. Aisle accessways not required to be accessible by the Minnesota Accessibility Code, Minnesota Rules, chapter 1341, shall provide a minimum 12 inches (305 mm) of width, plus 0.5 inch (12.7 mm) of width for each additional 1 foot (305 mm), or fraction thereof, beyond 12 feet (3, 658 mm) of aisle accessway length.

Exception: Portions of an aisle accessway having a length not exceeding 6 feet and used by a total of not more than four persons.

1018.2.2Minimum aisle width. The minimum clear width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm).

Exception: Nonpublic aisles serving fewer than 50 people, and that are not required to be accessible by the Minnesota Accessibility Code, Minnesota Rules, chapter 1341, need not exceed 28 inches (711 mm) in width.

1018.3Length.
1018.3.1Aisle accessway. The length of travel along the aisle accessway shall not exceed 30 feet ( 9,144 mm) to an aisle or exit access doorway.
1018.3.2Aisle. The length of travel along an aisle or combination aisle accessway and aisle to a point where a person has a choice of two or more paths of egress travel to separate exits or exit access doorways shall not exceed that permitted by Section 1006.2.1 for common path of egress travel.
Subpart 1.IFC Table 1018.1.

IFC Table 1018.1 is amended as follows:

TABLE 1018.1

CORRIDOR FIRE-RESISTANCE RATING

REQUIRED FIRE-RESISTANCE RATING(hours)
OCCUPANCYOCCUPANT LOAD SERVED BY CORRIDORWithout sprinkler systemWith sprinkler systemc
H-1, H-2, H-3AllNot permitted1
H-4, H-5Greater than 30Not permitted1
A, B, E, F, M, S, UGreater than 3010
RGreater than 1010.5
I-2a, I-4AllNot permitted0
I-1, I-3AllNot permitted1b

a. For requirements for occupancies in Group I-2, see IBC sections 407.2 and 407.3.
b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see IBC section 408.8.
c. Buildings equipped throughout with an automatic sprinkler system in accordance with section 903.3.1.1 or 903.3.1.2, where allowed.
Subp. 2.IFC section 1018.6.

IFC section 1018.6 is amended by modifying the exceptions to read as follows:

Exceptions:

1. Foyers, lobbies, or reception rooms constructed as required for corridors shall not be construed as intervening rooms if the aggregate area of these spaces does not exceed 1,000 square feet per floor.
2. Foyers, lobbies, or reception rooms that are more than 1,000 square feet per floor in aggregate area and other rooms or spaces that are constructed as required for corridors shall not be construed as intervening rooms when the rooms or spaces meet the following:
(a) The spaces are not occupied as dwelling units, sleeping units, incidental uses or hazardous uses.
(b) The rooms, spaces, or corridors are protected by an automatic smoke detection system that initiates alarm notification devices in all normally occupied rooms or spaces that use the corridor for a means of egress.
(c) The room or space is arranged so that it does not obstruct access to the required exits.
(d) Group R occupancies shall be provided with an automatic sprinkler system throughout to allow the use of exception #2.

Minn. R. Part 7511.1018

40 SR 1437
Renumbered from 7511.1017 44 SR 610, eff. 3/31/2020

Statutory Authority: MS s 326B.02