IFC section 1018 and all subsections are deleted in their entirety and replaced with the following:
SECTION 1018
AISLES
Exception: Doors, when fully opened, and handrails shall not reduce the required width by more than 7 inches (178 mm). Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections, such as trim and similar decorative features are permitted to project into the required width 1.5 inches (38 mm) from each side.
Exception: Portions of an aisle accessway having a length not exceeding 6 feet and used by a total of not more than four persons.
Exception: Nonpublic aisles serving fewer than 50 people, and that are not required to be accessible by the Minnesota Accessibility Code, Minnesota Rules, chapter 1341, need not exceed 28 inches (711 mm) in width.
IFC Table 1018.1 is amended as follows:
TABLE 1018.1
CORRIDOR FIRE-RESISTANCE RATING
REQUIRED FIRE-RESISTANCE RATING(hours) | |||
OCCUPANCY | OCCUPANT LOAD SERVED BY CORRIDOR | Without sprinkler system | With sprinkler systemc |
H-1, H-2, H-3 | All | Not permitted | 1 |
H-4, H-5 | Greater than 30 | Not permitted | 1 |
A, B, E, F, M, S, U | Greater than 30 | 1 | 0 |
R | Greater than 10 | 1 | 0.5 |
I-2a, I-4 | All | Not permitted | 0 |
I-1, I-3 | All | Not permitted | 1b |
IFC section 1018.6 is amended by modifying the exceptions to read as follows:
Exceptions:
Minn. R. agency 151, ch. 7511, pt. 7511.1018
Statutory Authority: MS s 326B.02