IFC section 905.2 is amended by adding subsections to read:
IFC section 905.3.1 is amended to read as follows:
Exception: Class I manual, automatic, or semiautomatic dry standpipes are allowed in buildings that are subject to freezing temperatures, provided that the hose connections are located as required for Class II standpipes in accordance with Section 905.5.
IFC section 905.3 is amended to read as follows:
Exception: Standpipe systems are not required in Group R-3 occupancies.
IFC section 905.3.2 is amended by adding a subsection to read:
IFC sections 905.3.4 and 905.3.4.1 are deleted and replaced with the following:
IFC section 905.3.6 is amended to read as follows:
IFC section 905.3 is amended by adding sections to read:
Exception: Combined systems meeting the provisions of Section 905.2 may be used.
When acceptable to the fire chief, fire department connections may be located inside all security walls or fences on the property.
Standpipes shall be located in accordance with Section 905. In addition, standpipes shall be located so that it will not be necessary to extend hose lines through smoke barriers. When located in cell complexes, standpipes may be located in secured pipe chases.
Permanent signage shall be required which reads "Fire Department Overhaul Hose Connection" at each connection in the building. If a separate standpipe system is provided, a sign shall also be provided at the exterior fire department connection.
IFC section 905.5.1 is deleted.
IFC section 905.6 and all subsections are deleted in their entirety.
Minn. R. Part 7511.0905
Statutory Authority: MS s 299F.011