Part 5225.1140 - ATTENDANCE OF HOBBY BOILERSSubpart 1. [Repealed, 21 SR 1897]Subp. 2. [Repealed, 21 SR 1897]Subp. 3.Hobby boiler.A hobby boiler may not be left unattended when in operation and members of the public are present. For purposes of this part, a traction engine may be considered as not being in operation when all of the following conditions exist:
A. the water level is at least one-third of the water gage glass;B. the header or dome valve is in a closed position;C. the draft doors are closed;D. the fire is banked or extinguished; andE. the boiler pressure is at least 20 pounds per square inch below the safety valve relieving pressure.Minn. R. agency 151, ch. 5225, LICENSES, pt. 5225.1140