IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subpart 1.Section 303.3.IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subp. 2.Section 303.3.1.IFGC section 303.3.1 is amended to read as follows:
303.3.1Fireplaces and decorative appliances in Group I-1, Condition 2 and Group I-2, Condition 2 occupancies. Direct-vent gas fireplaces shall be permitted inside smoke compartments containing dwelling units, sleeping rooms, and patient sleeping areas where all of the following conditions are met: 1. The direct-vent gas fireplaces are not located within a sleeping room.2. The direct-vent fireplaces have a sealed glass front with a wire mesh panel or screen.3. The controls for the direct-vent gas fireplace are located where they can be accessed only by facility staff.4. Electrically supervised carbon monoxide detection is provided in the room where the direct-vent gas fireplace is located.5. The direct-vent fireplace includes a guard in front of the glass where the glass temperature is equal to or exceeds 125°F (52°C).Minn. R. agency 151, ch. 1346, MINNESOTA FUEL GAS COD, pt. 1346.5303
REPEALED, 34 SR 537 39 SR 690; 44 SR 1085Statutory Authority: MS s 326B.02; 326B.101; 326B.106; 326B.13