ASHRAE 90.1 Table 6.8.2 is deleted and replaced with the following:
TABLE 6.8.2 Minimum Required Duct and Plenum Insulation
Ducts for Other Than Dwelling Units a,b | Supply Duct Requirements c,d | Return Duct Requirements c,d | Exhaust Duct and Relief Duct Requirements c,d,e,g |
Exterior of building | R-12, V and W | R-12, V and W | R-12, V and W |
Attics, garages, and ventilated crawl spaces | R-12 and V | R-12 and V | R-6 and V |
TD greater than 40°F | R-5 and V | None | R-5 and V |
TD greater than 15°F and less than or equal to 40°F | R-3.3 and V | None | R-3.3 and V |
Within concrete slab or within ground | R-3.5 and V | R-3.5 and V | None |
Within conditioned spaces | Nonef | None | None |
TD less than or equal to 15°F | None | None | None |
Ducts for Dwelling Unitsa | Requirementsc,d |
Exterior of building | R-12. V and W |
Attics, garages, and ventilated crawl spaces (except exhaust ducts) | R-12 and V |
Exhaust ducts in attics, garages, and ventilated crawl | |
spaces | R-3.3 and V |
Outdoor air intakes within conditioned spaces | R-3.3 and V |
Exhaust ducts within conditioned spacese | R-3.3 and V |
Within concrete slab or within ground | R-3.5 and V |
Within conditioned spaces | None |
°C=[(°F)-32]/1.8
ASHRAE 90.1 Table 6.8.3-1 is amended to add footnote "f" to read as follows: