ASHRAE 90.1 section 6.5.6.1.1 is amended by modifying exception 2 to read as follows:
ASHRAE 90.1 section 6.5.6.1.2 is amended to read as follows:
Each fan system serving spaces other than nontransient dwelling units shall have an energy recovery system where the design supply fan airflow rate exceeds the value listed in Table 6.5.6.1.2, based on the climate zone and percentage of outdoor air at design airflow conditions.
Exceptions:
Energy recovery systems required by this section shall result in an enthalpy recovery ratio of at least 50 percent. A 50 percent enthalpy recovery ratio shall mean a change in the enthalpy of the outdoor air supply equal to 50 percent of the difference between the outdoor air and entering exhaust air enthalpies at design conditions. The energy recovery system shall provide the required enthalpy recovery ratio at both heating and cooling design conditions unless one mode is not required for the climate zone by Exception 6.5.6.1.2.2.
Provision shall be made for both outdoor air and exhaust air to bypass or control the energy recovery system to enable economizer operation as required by Section 6.5.1.1. The bypass or control shall meet the following criteria:
Exception to 6.5.6.1.2.2:
Energy recovery systems with 80 percent or more outdoor air at full design airflow rate and not exceeding 10,000 cfm.
ASHRAE 90.1 Table 6.5.6.1.2-1 and Table 6.5.6.1.2-2 are deleted and replaced with the following:
Table 6.5.6.1.2 Exhaust Air Energy Recovery Requirements for Ventilation Systems
Percent (%) Outdoor Air At Full Design Airflow Rate | ||||||||
Climate Zone | > =10% and < 20% | >= 20% and < 30% | > =30% and < 40% | >= 40% and < 50% | >= 50% and < 60% | >= 60% and < 70% | >= 70% and < 80% | >= 80% |
Design Supply Fan Airflow Rate (cfm)
6A | NR | > 16.000 | > 5.500 | > 4.500 | > 3.500 | > 2.000 | > 1.000 | > 120 |
7 | NR | > 4.000 | > 2.500 | > 1.000 | > 140 | > 120 | > 100 | > 80 |
NR= Not required.
Minn. R. agency 151, ch. 1323, pt. 1323.0656