Minn. R. agency 151, ch. 1323, pt. 1323.0512

Current through Register Vol. 49, No. 24, December 9, 2024
Part 1323.0512 - SECTION 5.1.2, SPACE CONDITIONING CATEGORIES

ASHRAE 90.1 section 5.1.2.3.

The exception to ASHRAE 90.1 section 5.1.2.3 is amended to read as follows:

Exception to 5.1.2.3:

A space may be designated as either a semiheated space or an unconditioned space if approved by the building official. Unconditioned and semiheated spaces shall not be approved if there are automatic fire sprinkler systems unless those systems are designed to operate in below freezing temperatures. Signs indicating the maximum Btu heating input for semiheated spaces that is permissible by this standard shall be posted near the main entry location of the semiheated space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or the owners authorizing agent.

Minn. R. agency 151, ch. 1323, pt. 1323.0512

47 SR 983