Minn. R. agency 151, ch. 1311, pt. 1311.1006

Current through Register Vol. 49, No. 19, November 4, 2024
Part 1311.1006 - SECTION 1006, STRUCTURAL

Exception: Structural elements whose demand-capacity ratio considering the change of occupancy is not more than 105 percent of the demand-capacity ratio based on previously approved live loads. The evaluation of demand-capacity ratios and calculation of design gravity loads, forces, and capacities shall account for the cumulative effects of additions and alterations since original construction.

Minn. R. agency 151, ch. 1311, pt. 1311.1006

44 SR 487, eff. 3/31/2020