Section R403.1.4.1 is amended to read as follows:
Exception: Decks not supported by a dwelling need not be provided with footings that extend below the frost line.
IRC Section R403.1.6 is amended to read as follows:
Wood sole plates at all exterior walls on monolithic slabs wood sole plates of braced wall panels at building interiors on monolithic slabs, and all wood sill plates shall be anchored to the foundation with anchor bolts spaced a maximum of 6 feet (1829 mm) on center. Bolts shall be at least (12.7 mm) in diameter and shall extend a minimum of 7 inches (178 mm) into concreter or grouted cells of concrete masonry units. A nut and washer shall be tightened on each bolt. There shall be a minimum of two bolts per plate section with one bolt located not more than 12 inches (305 mm) or less than 7 bolt diameters from each end of the plate section. Interior bearing wall sole plates on monolithic slab foundation that are not part of a braced wall panel shall be positively anchored with approved fasteners. Sill plates and sole plates shall be protected against decay and termites where required by sections R317 and R318. Cold-formed steel framing systems shall be fastened to the wood sill plates or anchored directly to the foundation as required in section R505.3.1 or R603.1.1. When vertical reinforcing is required by other sections of this code, the foundation anchor bolts shall align with the reinforcing. All anchor bolts installed in masonry shall be grouted in place with at least 1-inch (25 mm) of grout between the bolt and the masonry.
Exceptions:
Minn. R. agency 151, ch. 1309, pt. 1309.0403
Statutory Authority: MS s 16B.59; 16B.61; 16B.64; 326B.101; 326B.106; 326B.13