Current through Register Vol. 48, No. 51, June 17, 2024
Part 1305.0403 - SECTION 403, HIGH-RISE BUILDINGSSubpart 1.IBC section 403.2.1.2.IBC section 403.2.1.2 is deleted in its entirety.
Subp. 3.IBC section 403.4.8.3.IBC section 403.4.8.3 is amended to read as follows:
403.4.8.3Standby power loads. The following are classified as standby power loads: 1. power and lighting for the fire command center required by Section 403.4.6;2. ventilation and automatic fire detection equipment for smokeproof enclosures; and3. passenger elevators serving occupied floors more than 75 feet (22, 860 mm) above the lowest level of fire department vehicle access.27 SR 1474; 32 SR 7; L 2007 c 140 art 4 s 61; art 13 s 4; L 2008 c 337 s 64; 39 SR 1605; 44 SR 610 eff. 3/31/2020Statutory Authority: MS s 16B.37; 16B.59 to 16B.76; 326B.101 to 326B.194