Part 4731.6080 - FIRE PROTECTION

For panoramic irradiators, the radiation room must have:

A. heat and smoke detectors, which must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly;
B. a system whereby the sources automatically become fully shielded if a fire is detected; and
C. a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas.