Part 4731.6080 - FIRE PROTECTION For panoramic irradiators, the radiation room must have:
A. heat and smoke detectors, which must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly;B. a system whereby the sources automatically become fully shielded if a fire is detected; andC. a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas.Minn. R. agency 144, ch. 4731, IRRADIATORS, pt. 4731.6080