Part 4658.4520 - VENTILATION PRESSURE RELATIONSHIPS AND VENTILATION FOR CERTAIN AREAS IN NURSING HOMES; EXISTING AND NEW CONSTRUCTION

Area DesignationPressure1 Relationship to Adjacent AreasAll Supply Air From OutdoorsMinimum Air Changes of Outdoor Air Per HourMinimum Total Air Changes Per HourAll Exhaust Directly To OutdoorsRecirculated Within Room
Resident Bedroom0-22--
Dayroom, Activity Area0-22--
Resident Corridor0-24--
Dining Room, Therapy--26--
Medication Room+-24--
Clean Utility Room+-24--
Soiled Utility Room---10YESNO
Toilet Room---10YESNO
Bathing Area---10YESNO
Barber and Beauty Room---10YESNO
Janitor's Closet---10YESNO
Sterilizer Equip. Room---10YESNO
Garbage Room, Can Washing---10YESNO
Trash Collection Room---10YESNO
Food Preparation, Nourishment0-210YESNO
Dishwashing, Food Cart Cleaning Area---10YESNO
Dietary Storage0--2-NO
Laundry Processing Room0-210YESNO
Soiled Linen Collection Room---10YESNO
Clean Linen Storage Room+-22--
Isolation Room--26YESNO
Smoking Room--210YESNO

Symbols:

Air Pressure Relationships:

+ = Positive;

- = Negative;

0 = Neutral

Air Changes, Supply, Exhaust:

- = Optional

1Areas with equal or positive pressure relationships to adjacent areas must be provided with tempered make-up air.

Minn. R. agency 144, ch. 4658, MECHANICAL SYSTEMS; NEW CONSTRUCTION, pt. 4658.4520

21 SR 196

Statutory Authority: MS s 144A.04; 144A.08