Part 4658.4605 - CORRIDOR RECEPTACLES; NEW CONSTRUCTION

Single receptacles on a separate circuit for equipment such as floor cleaning machines must be installed approximately 50 feet apart in all corridors and within 25 feet of ends of corridors.