Minn. R. agency 144, ch. 4645, MECHANICAL WORK FOR ALL HOSPITALS, pt. 4645.3805

Current through Register Vol. 49, No. 29, 2025
Part 4645.3805 - REFRIGERATION
Subpart 1.Extent of coverage.

This part shall include portable refrigerators, built-in refrigerators, garbage refrigerators, ice-making and refrigerator equipment, and morgue boxes.

Subp. 2.Box construction.

Boxes shall be lined with nonabsorbent sanitary material which will withstand the heavy use to which they will be subjected and shall be constructed so as to be easily cleaned. Refrigerators of adequate capacity shall be provided in all kitchens and other preparation centers where perishable foods will be stored. In the main kitchen, a minimum of two separate sections or boxes shall be provided, one for meats and dairy products, and one for general storage.

Subp. 3.Refrigerator machines.

Toxic, "irritant," or inflammable refrigerants shall not be used in refrigerator machines located in buildings occupied by patients. The compressors and evaporators shall have sufficient capacity to maintain temperatures of 35 degrees Fahrenheit in the meat and dairy boxes, and 40 degrees Fahrenheit in the general storage boxes when the boxes are being used normally. Compressors shall be automatically controlled.

Subp. 4.Tests.

Compressors, piping, and evaporators shall be tested for leaks and capacity.

Minn. R. agency 144, ch. 4645, MECHANICAL WORK FOR ALL HOSPITALS, pt. 4645.3805

Statutory Authority: MS s 144.55; 144.56