Minn. R. agency 144, ch. 4626, PHYSICAL FACILITY DESIGN AND CONSTRUCTION, pt. 4626.1345

Current through Register Vol. 49, No. 27, December 30, 2024
Part 4626.1345 - FLOOR AND WALL JUNCTURES; COVED AND ENCLOSED OR SEALED. 6-201.13
A. In food establishments in which cleaning methods other than water flushing are used for cleaning floors, the floor and wall junctures must be coved and closed to no larger than 1/32 inch (1 millimeter).
B. The floors in food establishments in which water flushing cleaning methods are used must be provided with drains and graded to drain, and the floor and wall junctures must be coved and sealed.

Minn. R. agency 144, ch. 4626, PHYSICAL FACILITY DESIGN AND CONSTRUCTION, pt. 4626.1345

23 SR 519
43 SR 295

Statutory Authority: MS s 31.101; 31.11; 144.05; 144.08; 144.12; 157.011