Mich. Admin. Code R. 29.7044

Current through Vol. 24-24, January 15, 2025
Section R. 29.7044 - Vehicle fueling appliances in nonresidential occupancies

Rule 44. Sections 4-7 to 4-7.7 of the storage and handling of gaseous and Liquefied H2 code are added as follows:

4-7 Vehicle fueling appliances (VFA) in nonresidential occupancies.

4-7.1 VFAs shall not exceed a gas flow of 36 scf/minute.

4-7.2 VFAs shall be listed.

4-7.3 VFAs may be used to fill stationary containers at vehicular fueling locations.

4-7.4 A VFAs installed with storage containers shall comply with the provisions of chapters 2, 3, and 4.

4-7.5 The installation of VFAs at a residence shall comply with the requirements of section 4-9.

4-7.6 Where more than 1 VFA are located in a common area, spacing between the VFAs shall not be less than 3 feet (1 meter), unless permitted in the manufacturer's recommendations.

4-7.7 Unless specifically permitted in the manufacture's recommendations, multiple VFAs shall not be manifolded together on the discharge side.

Mich. Admin. Code R. 29.7044

2008 AACS